Adrbog.com DanskEnglishFrançais — coming soonDeutsch — coming soon ADR 2025 Reference Tool
Lite Pro

Packing instruction P200

ADR 2025 — packing instruction P200, Chapter 4.1.

P200 PACKING INSTRUCTION P200 Type of packagings: Cylinders, tubes, pressure drums and bundles of cylinders Cylinders, tubes, pressure drums and bundles of cylinders are authorised provided the special packing provisions of 4.1.6, the provisions listed below under (1) to (9) and, when referred to in the column "Special packing provisions" of tables 1, 2 or 3, the relevant special packing provisions listed below under (10), are met. General (1) Pressure receptacles shall be so closed and leakproof as to prevent escape of the gases. (2) Pressure receptacles containing toxic substances with an LC₅₀ less than or equal to 200 ml/m³ (ppm) as specified in the table shall not be equipped with any pressure relief device. Pressure relief devices shall be fitted on UN pressure receptacles used for the carriage of UN No. 1013 carbon dioxide and UN No. 1070 nitrous oxide. (3) The following three tables cover compressed gases (Table 1), liquefied and dissolved gases (Table 2) and substances not in Class 2 (Table 3). They provide: (a) The UN number, name and description, and the classification code of the substance; (b) The LC₅₀ for toxic substances; (c) The types of pressure receptacles authorised for the substance, shown by the letter "X"; (d) The maximum test period for periodic inspection of the pressure receptacles; NOTE: For pressure receptacles which make use of composite materials, the maximum test period shall be 5 years. The test period may be extended to that specified in Tables 1 and 2 (i.e. up to 10 years), if approved by the competent authority or body designated by this authority which issued the type approval. (e) The minimum test pressure of the pressure receptacles; (f) The maximum working pressure of the pressure receptacles for compressed gases (where no value is given, the working pressure shall not exceed two thirds of the test pressure) or the maximum filling ratio(s) dependent on the test pressure(s) for liquefied and dissolved gases; (g) Special packing provisions that are specific to a substance. Test pressure, filling ratios and filling requirements (4) The minimum test pressure required for is 1 MPa (10 bar). (5) In no case shall pressure receptacles be filled in excess of the limit permitted in the following requirements: (a) For compressed gases, the working pressure shall be not more than two thirds of the test pressure of the pressure receptacles. Restrictions to this upper limit on working pressure are imposed by (10), special packing provision "o". In no case shall the internal pressure at 65 °C exceed the test pressure. (b) For high pressure liquefied gases, the filling ratio shall be such that the settled pressure at 65 °C does not exceed the test pressure of the pressure receptacles. The use of test pressures and filling ratios other than those in the table is permitted, except where (10), special packing provision "o" applies, provided that: (i) the criterion of (10), special packing provision "r" is met when applicable; or (ii) the above criterion is met in all other cases. For high pressure liquefied gases and gas mixtures for which relevant data are not available, the maximum filling ratio (FR) shall be determined as follows: FR = 8.5 × 10-4 × dg × Ph where: FR = maximum filling ratio dg = gas density (at 15 °C, 1 bar)(in kg/m³) Ph = minimum test pressure (in bar) Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 If the density of the gas is unknown, the maximum filling ratio shall be determined as follows: FR = Ph × MM × 10-3 R × 338 where: FR = maximum filling ratio Ph = minimum test pressure (in bar) MM = molecular mass (in g/mol) R = 8.31451  10-2 bar·l·mol-1·K-1 (gas constant). For gas mixtures, the average molecular mass is to be taken, taking into account the volumetric concentrations of the various components. (c) For low pressure liquefied gases, the maximum mass of contents per litre of water capacity shall equal 0.95 times the density of the liquid phase at 50 °C; in addition, the liquid phase shall not fill the pressure receptacle at any temperature up to 60 °C. The test pressure of the pressure receptacle shall be at least equal to the vapour pressure (absolute) of the liquid at 65 °C, minus 100 kPa (1 bar). For low pressure liquefied gases and gas mixtures for which relevant data are not available, the maximum filling ratio shall be determined as follows: FR = (0.0032 × BP - 0.24) × d1 where: FR = maximum filling ratio BP = boiling point (in Kelvin) d1 = density of the liquid at boiling point (in kg/l); (d) For UN No. 1001 acetylene, dissolved, and UN No. 3374 acetylene, solvent free, see (10), special packing provision "p". (e) For liquefied gases charged with compressed gases, both components – the liquefied gas and the compressed gas – have to be taken into consideration in the calculation of the internal pressure in the pressure receptacle. The maximum mass of contents per litre of water capacity shall not exceed 0.95 times the density of the liquid phase at 50 °C; in addition, the liquid phase shall not completely fill the pressure receptacle at any temperature up to 60 °C. When filled, the internal pressure at 65 °C shall not exceed the test pressure of the pressure receptacles. The vapour pressures and volumetric expansions of all substances in the pressure receptacles shall be considered. When experimental data is not available, the following steps shall be carried out: (i) Calculation of the vapour pressure of the liquefied gas and of the partial pressure of the compressed gas at 15 °C (filling temperature); (ii) Calculation of the volumetric expansion of the liquid phase resulting from the heating from 15 °C to 65 °C and calculation of the remaining volume for the gaseous phase; (iii) Calculation of the partial pressure of the compressed gas at 65 °C considering the volumetric expansion of the liquid phase; NOTE: The compressibility factor of the compressed gas at 15 °C and 65 °C shall be considered. (iv) Calculation of the vapour pressure of the liquefied gas at 65 °C; (v) The total pressure is the sum of the vapour pressure of the liquefied gas and the partial pressure of the compressed gas at 65 °C; (vi) Consideration of the solubility of the compressed gas at 65 °C in the liquid phase; The test pressure of the pressure receptacle shall not be less than the calculated total pressure minus 100 kPa (1bar). If the solubility of the compressed gas in the liquid phase is not known for the calculation, the test pressure can be calculated without taking the gas solubility (subparagraph (vi)) into account. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 (6) Other test pressure and filling ratio may be used provided they satisfy the general requirements outlined in paragraphs (4) and (5) above. (7) (a) The filling of pressure receptacles may only be carried out by speciallyequipped centres, with qualified staff using appropriate procedures. The procedures should include checks: (i) Of the conformity of receptacles and accessories with ADR; (ii) Of their compatibility with the product to be carried; (iii) Of the absence of damage which might affect safety; (iv) Of compliance with the filling ratio or pressure of filling, as appropriate; (v) Of marks and identification. (b) LPG to be filled in cylinders shall be of high quality; this is deemed to be fulfilled if the LPG to be filled is in compliance with the limitations on corrosiveness as specified in ISO 9162:1989. Periodic inspections (8) Refillable pressure receptacles shall be subjected to periodic inspections in accordance with the requirements of 6.2.1.6 and 6.2.3.5 respectively. (9) If special provisions for certain substances do not appear in the tables below, periodic inspections shall be carried out: (a) Every 5 years in the case of pressure receptacles intended for the carriage of gases of classification codes 1T, 1TF, 1TO, 1TC, 1TFC, 1TOC, 2T, 2TO, 2TF, 2TC, 2TFC, 2TOC, 4A, 4F and 4TC; (b) Every 5 years in the case of pressure receptacles intended for the carriage of substances from other classes; (c) Every 10 years in the case of pressure receptacles intended for the carriage of gases of classification codes 1A, 1O, 1F, 2A, 2O and 2F. For pressure receptacles which make use of composite materials, the maximum test period shall be 5 years. The test period may be extended to that specified in Tables 1 and 2 (i.e. up to 10 years), if approved by the competent authority or body designated by this authority which issued the type approval. Special packing provisions (10) Material compatibility a: Aluminium alloy pressure receptacles shall not be used. b: Copper valves shall not be used. c: Metal parts in contact with the contents shall not contain more than 65 % copper. d: When steel pressure receptacles or composite pressure receptacles with steel liners are used, only those bearing the "H" mark in accordance with 6.2.2.7.4 (p) are permitted. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 Requirements for toxic substances with an LC₅₀ less than or equal to 200 ml/m³ (ppm) k: Valve outlets shall be fitted with pressure retaining gastight plugs or caps having threads that match those of the valve outlets and made of material not liable to attack by the contents of the pressure receptacle. Each cylinder within a bundle shall be fitted with an individual valve that shall be closed during carriage. After filling, the manifold shall be evacuated, purged and plugged. Bundles containing UN No. 1045 Fluorine, compressed, may be constructed with isolation valves on groups of cylinders not exceeding 150 litres total water capacity instead of isolation valves on every cylinder. Cylinders and individual cylinders within a bundle shall have a test pressure greater than or equal to 200 bar and a minimum wall thickness of 3.5 mm for aluminium alloy or 2 mm for steel. Individual cylinders not complying with this requirement shall be carried in a rigid outer packaging that will adequately protect the cylinder and its fittings and meeting the packing group I performance level. Pressure drums shall have a minimum wall thickness as specified by the competent authority. Pressure receptacles shall not be fitted with a pressure relief device. Cylinders and individual cylinders in a bundle shall be limited to a maximum water capacity of 85 litres. Each valve shall be capable of withstanding the test pressure of the pressure receptacle and be connected directly to the pressure receptacle by either a taper thread or other means which meets the requirements of ISO 10692-2:2001. Each valve shall either be of the packless type with nonperforated diaphragm, or be of a type which prevents leakage through or past the packing. Carriage in capsules is not allowed. Each pressure receptacle shall be tested for leakage after filling. Gas specific provisions l: UN No. 1040 ethylene oxide may also be packed in hermetically sealed glass or metal inner packagings suitably cushioned in fibreboard, wooden or metal boxes meeting the packing group I performance level. The maximum quantity permitted in any glass inner packaging is 30 g, and the maximum quantity permitted in any metal inner packaging is 200 g. After filling, each inner packaging shall be determined to be leaktight by placing the inner packaging in a hot water bath at a temperature, and for a period of time, sufficient to ensure that an internal pressure equal to the vapour pressure of ethylene oxide at 55 °C is achieved. The maximum net mass in any outer packaging shall not exceed 2.5 kg. m: Pressure receptacles shall be filled to a working pressure not exceeding 5 bar. n: Cylinders and individual cylinders in a bundle shall contain not more than 5 kg of the gas. When bundles containing UN No. 1045 Fluorine, compressed are divided into groups of cylinders in accordance with special packing provision "k" each group shall contain not more than 5 kg of the gas. o: In no case shall the working pressure or filling ratio shown in the tables be exceeded. p: For UN No. 1001 acetylene, dissolved, and UN No. 3374 acetylene, solvent free: cylinders shall be filled with a homogeneous monolithic porous material; the working pressure and the quantity of acetylene shall not exceed the values prescribed in the approval or in ISO 3807 1:2000, ISO 3807-2:2000 or ISO 3807:2013, as applicable. For UN No. 1001 acetylene, dissolved: cylinders shall contain a quantity of acetone or suitable solvent as specified in the approval (see ISO 3807-1:2000, ISO 3807-2:2000 or ISO 3807:2013 as applicable); cylinders manifolded together shall be carried vertically. Alternatively, for UN No. 1001 acetylene, dissolved: cylinders which are not UN pressure receptacles may be filled with a non monolithic porous material; the working pressure, the quantity of acetylene and the quantity of solvent shall not exceed the values prescribed in the approval. The maximum test period for periodic inspection of the cylinders shall not exceed five years. q: Valve outlets of pressure receptacles for pyrophoric gases or flammable mixtures of gases containing more than 1 % of pyrophoric compounds shall be fitted with gastight plugs or caps which shall be made of material not liable to attack by the contents of the pressure receptacle. When these pressure receptacles are manifolded in a bundle, each of the pressure receptacles shall be fitted with an individual valve that shall be closed during carriage, and the outlet of the manifold valve shall be fitted with a pressure retaining gastight plug or cap. Gastight plugs or caps shall have threads that match those of the valve outlets. Carriage in capsules is not allowed. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 r: The filling ratio of this gas shall be limited such that, if complete decomposition occurs, the pressure does not exceed two thirds of the test pressure of the pressure receptacle. ra: This gas may also be packed in capsules under the following conditions: (a) The mass of gas shall not exceed 150 g per capsule; (b) The capsules shall be free from faults liable to impair the strength; (c) The leakproofness of the closure shall be ensured by an additional device (cap, crown, seal, binding, etc.) capable of preventing any leakage of the closure during carriage; (d) The capsules shall be placed in an outer packaging of sufficient strength. A package shall not weigh more than 75 kg. s: Aluminium alloy pressure receptacles shall be: (a) Equipped only with brass or stainless steel valves; and (b) Cleaned for hydrocarbons contamination and not contaminated with oil. UN pressure receptacles shall be cleaned in accordance with ISO 11621:1997. ta: Other criteria may be used for filling of welded steel cylinders intended for the carriage of substances of UN No. 1965: (a) With the agreement of the competent authorities of the countries where the carriage is carried out; and (b) In compliance with the provisions of a national code or standard recognised by the competent authorities. When the criteria for filling are different from those in P200(5), the transport document shall include the statement "Carriage in accordance with packing instruction P200, special packing provision ta" and the indication of the reference temperature used for the calculation of the filling ratio. Periodic inspection u: The interval between periodic tests may be extended to 10 years for aluminium alloy pressure receptacles. This derogation may only be applied to UN pressure receptacles when the alloy of the pressure receptacle has been subjected to stress corrosion testing as specified in ISO 7866:2012 + Cor 1: 2014. ua: The interval between periodic tests may be extended to 15 years for aluminium alloy cylinders and bundles of such cylinders if the provisions of paragraph (13) of this packing instruction are applied. This shall not apply to cylinders made from aluminium alloy AA 6351. For mixtures, this provision "ua" may be applied provided all the individual gases in the mixture have been allocated "ua" in Table 1 or Table 2. v: (1) The interval between inspections for steel cylinders, other than refillable welded steel cylinders for UN Nos. 1011, 1075, 1965, 1969 or 1978, may be extended to 15 years: (a) With the agreement of the competent authority (authorities) of the country (countries) where the periodic inspection and the carriage take place; and (b) In accordance with the requirements of a technical code or a standard recognised by the competent authority (2) For refillable welded steel cylinders for UN Nos. 1011, 1075, 1965, 1969 or 1978, the interval may be extended to 15 years, if the provisions of paragraph (12) of this packing instruction are applied. va: For seamless steel cylinders which are equipped with residual pressure valves (RPVs) (see note below) that have been designed and tested in accordance with EN ISO 15996:2005 + A1:2007 or EN ISO 15996:2017 and for bundles of seamless steel cylinders equipped with main valve(s) with a residual pressure device, tested in accordance with EN ISO 15996:2005 + A1:2007 or EN ISO 15996:2017, the interval between periodic tests may be extended to 15 years if the provisions of paragraph (13) of this packing instruction are applied. For mixtures, this provision "va" may be applied provided all the individual gases in the mixture have been allocated "va" in Table 1 or Table 2. NOTE: "Residual Pressure Valve" (RPV) means a closure which incorporates a residual pressure device that prevents ingress of contaminants by maintaining a positive differential between the pressure within the cylinder and the valve outlet. In order to prevent backflow of fluids into the cylinder from a higher pressure source a "Non-Return Valve" (NRV) function shall either be incorporated into the residual pressure device or be a discrete additional device in the cylinder valve, e.g. a regulator. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 Requirements for N.O.S. entries and for mixtures z: The construction materials of the pressure receptacles and their accessories shall be compatible with the contents and shall not react to form harmful or dangerous compounds therewith. The test pressure and filling ratio shall be calculated in accordance with the relevant requirements of (5). Toxic substances with an LC₅₀ less than or equal to 200 ml/m³ shall not be carried in tubes, pressure drums or MEGCs and shall meet the requirements of special packing provision "k". However, UN No. 1975 Nitric oxide and dinitrogen tetroxide mixture may be carried in pressure drums. For pressure receptacles containing pyrophoric gases or flammable mixtures of gases containing more than 1 % pyrophoric compounds, the requirements of special packing provision "q" shall be met. The necessary steps shall be taken to prevent dangerous reactions (i.e. polymerisation or decomposition) during carriage. If necessary, stabilisation or addition of an inhibitor shall be required. Mixtures containing UN No. 1911 diborane, shall be filled to a pressure such that, if complete decomposition of the diborane occurs, two thirds of the test pressure of the pressure receptacle shall not be exceeded. Mixtures containing UN No. 2192 germane, other than mixtures of up to 35 % germane in hydrogen or nitrogen or up to 28 % germane in helium or argon, shall be filled to a pressure such that, if complete decomposition of the germane occurs, two thirds of the test pressure of the pressure receptacle shall not be exceeded. Mixtures of fluorine and nitrogen with a fluorine concentration below 35 % by volume may be filled in pressure receptacles up to a maximum allowable working pressure for which the partial pressure of fluorine does not exceed 3.1 MPa (31 bar) absolute. working pressure (bar) < 31 xf - 1 where: xf = fluorine concentration in % by volume/100. Mixtures of fluorine and inert gases with a fluorine concentration below 35 % by volume may be filled in pressure receptacles up to a maximum allowable working pressure for which the partial pressure of fluorine does not exceed 3.1 MPa (31 bar) absolute, additionally taking the coefficient of nitrogen equivalency in accordance with ISO 10156:2017 into account when calculating the partial pressure. working pressure (bar) < 31 xf (xf + Kk × xk) - 1 where: xf = fluorine concentration in % by volume/100; Kk = coefficient of equivalency of an inert gas relative to nitrogen (coefficient of nitrogen equivalency); xk = inert gas concentration in % by volume/100. However, the working pressure for mixtures of fluorine and inert gases shall not exceed 20 MPa (200 bar). The minimum test pressure of pressure receptacles for mixtures of fluorine and inert gases equals 1.5 times the working pressure or 20 MPa (200 bar), with the greater value to be applied. Requirements for substances not in Class 2 ab: Pressure receptacles shall satisfy the following conditions: (a) The pressure test shall include an inspection of the inside of the pressure receptacles and check of accessories; (b) In addition resistance to corrosion shall be checked every two years by means of suitable instruments (e.g. ultrasound) and the condition of the accessories verified; (c) Wall thickness shall not be less than 3 mm. ac: Tests and inspections shall be carried out under the supervision of an expert approved by the competent authority. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 ad: Pressure receptacles shall satisfy the following conditions: (a) Pressure receptacles shall be designed for a design pressure of not less than 2.1 MPa (21 bar) (gauge pressure); (b) In addition to the marks for refillable receptacles, the pressure receptacles shall bear the following particulars in clearly legible and durable characters: (i) The UN number and the proper shipping name of the substance according to 3.1.2; (ii) The maximum permitted mass when filled and the tare of the pressure receptacle, including accessories fitted during filling, or the gross mass. (11) The applicable requirements of this packing instruction are considered to have been complied with if the following standards, as relevant, are applied: Applicable requirements Reference Titile of document (7) EN 13365:2002 +A1:2005 Transportable gas cylinders – Cylinder bundles for permanent and liquefied gases (excluding acetylene) – Inspection at the time of filling (7) EN ISO 24431:2016 Gas cylinders – Seamless, welded and composite cylinders for compressed and liquefied gases (excluding acetylene) – Inspection at time of filling (7) (a) ISO 10691:2004 Gas cylinders – Refillable welded steel cylinders for liquefied petroleum gas (LPG) – Procedures for checking before, during and after filling. (7) (a) ISO 11755:2005 Gas cylinders – Cylinder bundles for compressed and liquefied gases (excluding acetylene) – Inspection at time of filling (7) (a) and (10) p EN ISO 11372:2011 Gas cylinders – Acetylene cylinders – Filling conditions and filling inspection (7) (a) and (10) p EN ISO 13088:2012 + A1:2020 Gas cylinders – Acetylene cylinder bundles – Filling conditions and filling inspection (7) and (10) ta (b) EN 1439:2021 LPG equipment and accessories – Procedure for checking transportable refillable LPG cylinders before, during and after filling (7) and (10) ta (b) EN 13952:2017 LPG equipment and accessories – Filling operations for LPG cylinders (12) An interval of 15 years for the periodic inspection of refillable welded steel cylinders may be granted in accordance with special packing provision v (2) of paragraph (10), if the following provisions are applied. 1. General provisions 1.1 For the application of this section, the competent authority shall not delegate its tasks and duties to Xb bodies (inspection bodies of type B) or IS (inhouse inspection services) (for the definitions of Xb and IS, see 6.2.3.6.1). 1.2 The owner of the cylinders shall apply to the competent authority for granting the 15 year interval, and shall demonstrate that the requirements of subparagraphs 2, 3 and 4 are met. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 1.3 Cylinders manufactured since 1 January 1999 shall have been manufactured in conformity with the following standards: - EN 1442; or - EN 13322-1; or - Annex I, parts 1 to 3 to Council Directive 84/527/EECa as applicable according to the table in 6.2.4. Other cylinders manufactured before 1 January 2009 in conformity with ADR in accordance with a technical code accepted by the national competent authority may be accepted for a 15 year interval, if they are of equivalent safety to the provisions of ADR as applicable at the time of application. 1.4 The owner shall submit documentary evidence to the competent authority demonstrating that the cylinders comply with the provisions of subparagraph 1.3. The competent authority shall verify that these conditions are met. 1.5 The competent authority shall check whether the provisions of subparagraphs 2 and 3 are fulfilled and correctly applied. If all provisions are fulfilled, it shall authorise the 15-year interval for the cylinders. In this authorisation, the type of cylinder (as specified in the type approval) or a group of cylinders (see note) covered shall be clearly identified. The authorisation shall be delivered to the owner; the competent authority shall keep a copy. The owner shall keep the documents for as long as the cylinders are authorised for a 15 year interval. NOTE: A group of cylinders is defined by the production dates of identical cylinders for a period, during which the applicable provisions of ADR and of the technical code accepted by the competent authority have not changed in their technical content. Example: Cylinders of identical design and volume having been manufactured according to the provisions of ADR as applicable between 1 January 1985 and 31 December 1988 in combination with a technical code accepted by the competent authority applicable for the same period, form one group in terms of the provisions of this paragraph. 1.6 The competent authority shall monitor the owner of the cylinders for compliance with the provisions of ADR and the authorisation given as appropriate, but at least every three years or when changes to the procedures are introduced. 2. Operational provisions 2.1 Cylinders having been granted a 15 year interval for periodic inspection shall only be filled in filling centres applying a documented quality system to ensure that all the provisions of paragraph (7) of this packing instruction and the requirements and responsibilities of EN 1439:2021 (or until 31 December 2024, EN 1439:2017) and EN 13952:2017 are fulfilled and correctly applied. 2.2 The competent authority shall verify that these requirements are fulfilled and check this as appropriate, but at least every three years or when changes to the procedures are introduced. 2.3 The owner shall provide documentary evidence to the competent authority that the filling centre complies with the provisions of subparagraph 2.1. 2.4 If a filling centre is situated in a different Contracting Party to ADR, the owner shall provide additional documentary evidence that the filling centre is monitored accordingly by the competent authority of that Contracting Party to ADR. 2.5 To prevent internal corrosion, only gases of high quality with very low potential contamination shall be filled into the cylinders. This is deemed to be fulfilled, if the gases conform to the limitations on corrosiveness as specified in ISO 9162:1989. a Council directive on the approximation of the laws of the Member States relating to welded unalloyed steel gas cylinders, published in the Official Journal of the European Communities No. L 300 of 19.11.1984. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 3. Provisions for qualification and periodic inspection 3.1 Cylinders of a type or group already in use, for which a 15 year interval has been granted and to which the 15 year interval has been applied, shall be subject to a periodic inspection according to 6.2.3.5. NOTE: For the definition of a group of cylinders, see Note to sub paragraph 1.5. 3.2 If a cylinder with a 15-year interval fails the hydraulic pressure test during a periodic inspection e.g. by bursting or leakage, the owner shall investigate and produce a report on the cause of the failure and if other cylinders (e.g. of the same type or group) are affected. In the latter case, the owner shall inform the competent authority. The competent authority shall then decide on appropriate measures and inform the competent authorities of all other Contracting Parties to ADR accordingly. 3.3 If internal corrosion as defined in the standard applied (see subparagraph 1.3) has been detected, the cylinder shall be withdrawn from use and shall not be granted any further period for filling and carriage. 3.4 Cylinders having been granted a 15 year interval shall only be fitted with valves designed and manufactured for a minimum 15 year period of use according to EN 13152:2001 + A1:2003, EN 13153:2001 + A1:2003, EN ISO 14245:2010, EN ISO 14245:2019, EN ISO 14245:2021, EN ISO 15995:2010, EN ISO 15995:2019 or EN ISO 15995:2021. After a periodic inspection, a new valve shall be fitted to the cylinder, except that manually operated valves, which have been refurbished or inspected according to EN 14912:2022 may be refitted, if they are suitable for another 15 year period of use. Refurbishment or inspection shall only be carried out by the manufacturer of the valves or according to his technical instruction by an enterprise qualified for such work and operating under a documented quality system. 4. Marking Cylinders having been granted a 15 year interval for periodic inspection in accordance with this paragraph shall additionally be marked clearly and legibly with "P15Y". This mark shall be removed if the cylinder is no longer authorised for a 15 year interval. NOTE: This mark shall not apply to cylinders subject to the transitional provision in 1.6.2.9, 1.6.2.10 or the provisions of special packing provision v (1) of paragraph (10) of this packing instruction. (13) An interval of 15 years for the periodic inspection of seamless steel and aluminium alloy cylinders and bundles of such cylinders may be granted in accordance with special packing provisions ua or va of paragraph (10), if the following provisions are applied: 1. General provisions 1.1 For the application of this paragraph, the competent authority shall not delegate its tasks and duties to Xb bodies (inspection bodies of type B) or IS (inhouse inspection services) (for the definitions of Xb and IS, see 6.2.3.6.1). 1.2 The owner of the cylinders or bundles of cylinders shall apply to the competent authority for granting the 15 year interval, and shall demonstrate that the requirements of subparagraphs 2, 3 and 4 are met. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 1.3 Cylinders manufactured since 1 January 1999 shall have been manufactured in conformity with one of the following standards: - EN 1964-1 or EN 1964-2; or - EN 1975; or - EN ISO 9809-1 or EN ISO 9809-2; or - EN ISO 7866; or - Annex I, parts 1 to 3 to Council Directive 84/525/EECb and 84/526/EECc as applicable at the time of manufacture (see also the table in 6.2.4.1). Other cylinders manufactured before 1 January 2009 in conformity with ADR in accordance with a technical code accepted by the national competent authority may be accepted for a 15 year interval for periodic inspection, if they are of equivalent safety to the provisions of ADR as applicable at the time of application. NOTE: This provision is considered to be fulfilled if the cylinder has been reassessed according to the procedure for the reassessment of conformity described in Annex III of Directive 2010/35/EU of 16 June 2010 or Annex IV, Part II, of Directive 1999/36/EC of 29 April 1999. 6.2.2.7.2 (a) shall not be granted a 15 year interval for periodic inspection. 1.4 Bundles of cylinders shall be constructed such that contact between cylinders along the longitudinal axis of the cylinders does not result in external corrosion. The supports and restraining straps shall be such as to minimise the risk of corrosion to the cylinders. Shock absorbent materials used in supports shall only be allowed if they have been treated to eliminate water absorption. Examples of suitable materials are waterresistant belting and rubber. 1.5 The owner shall submit documentary evidence to the competent authority demonstrating that the cylinders comply with the provisions of subparagraph 1.3. The competent authority shall verify that these conditions are met. 1.6 The competent authority shall check whether the provisions of subparagraphs 2 and 3 are fulfilled and correctly applied. If all provisions are fulfilled, it shall authorise the 15 year interval for periodic inspection for the cylinders or bundles of cylinders. In this authorisation a group of cylinders (see note below) covered shall be clearly identified. The authorisation shall be delivered to the owner; the competent authority shall keep a copy. The owner shall keep the documents for as long as the cylinders are authorised for a 15 year interval. NOTE: A group of cylinders is defined by the production dates of identical cylinders for a period, during which the applicable provisions of ADR and of the technical code accepted by the competent authority have not changed in their technical content. Example: Cylinders of identical design and volume having been manufactured according to the provisions of ADR applicable between 1 January 1985 and 31 December 1988 in combination with a technical code accepted by the competent authority applicable for the same period form one group in terms of the provisions of this paragraph. 1.7 The owner shall ensure compliance with the provisions of ADR and the authorisation given as appropriate and shall demonstrate this to the competent authority on request but at least every three years or when significant changes to the procedures are introduced. b Council Directive on the approximation of the laws of the Member States relating to seamless, steel gas cylinders, published in the Official Journal of the European Communities No. L 300 of 19.11.1984. c Council Directive on the approximation of the laws of the Member States relating to seamless, unalloyed aluminium and aluminium alloy gas cylinders, published in the Official Journal of the European Communities No. L 300 of 19.11.1984. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 2. Operational provisions 2.1 Cylinders or bundles of cylinders having been granted a 15 year interval for periodic inspection shall only be filled in filling centres applying a documented and certified quality system to ensure that all the provisions of paragraph (7) of this packing instruction and the requirements and responsibilities of EN ISO 24431:2016 or EN 13365:2002 as applicable are fulfilled and correctly applied. The quality system, according to the ISO 9000 (series) or equivalent, shall be certified by an accredited independent body recognized by the competent authority. This includes procedures for preand postfill inspections and the filling process for cylinders, bundles of cylinders and valves. 2.2 Aluminium alloy cylinders and bundles of such cylinders without RPVs having been granted a 15 year interval for periodic inspection shall be checked prior to every fill in accordance with a documented procedure which shall at least include the following: (a) Open the cylinder valve or the main valve of the bundle of cylinders to check for residual pressure; (b) If gas is emitted, the cylinder or bundle of cylinders may be filled; (c) If no gas is emitted, the internal condition of the cylinder or bundle of cylinders shall be checked for contamination; (d) If no contamination is detected, the cylinder or bundle of cylinders may be filled. (e) If contamination is detected corrective action is to be carried out. 2.3 Seamless steel cylinders fitted with RPVs and bundles of seamless steel cylinders equipped with main valve(s) with a residual pressure device having been granted a 15 year interval for periodic inspection shall be checked prior to every fill in accordance with a documented procedure which shall at least include the following: (a) Open the cylinder valve or bundle of cylinders main valve to check for residual pressure; (b) If gas is emitted, the cylinder or bundle of cylinders may be filled; (c) If no gas is emitted the functioning of the residual pressure device shall be checked; (d) If the check shows that the residual pressure device has retained pressure the cylinder or bundle of cylinders may be filled; (e) If the check shows that the residual pressure device has not retained pressure, the internal condition of the cylinder or bundle of cylinders shall be checked for contamination: (i) If no contamination is detected, the cylinder or bundle of cylinders may be filled following repair or replacement of the residual pressure device; (ii) If contamination is detected, a corrective action shall be carried out. 2.4 To prevent internal corrosion, only gases of high quality with very low potential contamination shall be filled into cylinders or bundles of cylinders. This is deemed to be fulfilled, if the compatibility of gases/material is acceptable in accordance with EN ISO 11114-1:2020 + A1:2023 and EN ISO 11114- 2:2021, and the gas quality meets the specifications in EN ISO 14175:2008 or, for gases not covered in the standard, a minimum purity of 99.5 % by volume and a maximum moisture content of 40 ml/m³ (ppm). For nitrous oxide the values shall be a minimum purity of 98 % by volume and a maximum moisture content of 70 ml/m³ (ppm). 2.5 The owner shall ensure that the requirements of 2.1 to 2.4 are fulfilled and provide documentary evidence of this to the competent authority on request, but at least every three years or when significant changes to the procedures are introduced. 2.6 If a filling centre is situated in a different Contracting Party to ADR, the owner shall provide to the competent authority, on request, additional documentary evidence that the filling centre is monitored accordingly by the competent authority of that Contracting Party to ADR. See also 1.2. Cont'd on next page P200 PACKING INSTRUCTION (cont’d) P200 3. Provisions for qualification and periodic inspection 3.1 Cylinders and bundles of cylinders already in use, for which the conditions of subparagraph 2 have been met from the date of the last periodic inspection to the satisfaction of the competent authority, may have their inspection period extended to 15 years from the date of the last periodic inspection. Otherwise the change of test period from ten to fifteen years shall be made at the time of periodic inspection. The periodic inspection report shall indicate that this cylinder or bundle of cylinders shall be fitted with a residual pressure device as appropriate. Other documentary evidence may be accepted by the competent authority. 3.2 If a cylinder with a 15 year interval fails the pressure test by bursting or leakage or if a severe defect is detected by a nondestructive test (NDT) during a periodic inspection the owner shall investigate and produce a report on the cause of the failure and if other cylinders (e.g. of the same type or group) are affected. In the latter case, the owner shall inform the competent authority. The competent authority shall then decide on appropriate measures and inform the competent authorities of all other Contracting Parties to ADR accordingly. 3.3 If internal corrosion and other defects as defined in the periodic inspection standards referenced in 6.2.4 have been detected, the cylinder shall be withdrawn from use and shall not be granted any further period for filling and carriage. 3.4 Cylinders or bundles of cylinders having been granted a 15 year interval for periodic inspection shall only be fitted with valves designed and tested according to EN 849 or EN ISO 10297 as applicable at the time of manufacture (see also the table in 6.2.4.1). After a periodic inspection a new valve shall be fitted, except that valves which have been refurbished or inspected according to EN ISO 22434:2022 may be refitted. 4. Marking Cylinders and bundles of cylinders having been granted a 15 year interval for periodic inspection in accordance with this paragraph shall have the date (year) of the next periodic inspection as required in section 5.2.1.6 (c) and at the same time additionally be marked clearly and legibly with "P15Y". This mark shall be removed if the cylinder or bundle of cylinders is no longer authorised for a 15 year interval for periodic inspection. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 1: COMPRESSED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar e Maximum working pressure, bar e Special packing provisions 1002 AIR, COMPRESSED 1A X X X X 10 ua, va 1006 ARGON, COMPRESSED 1A X X X X 10 ua, va 1016 CARBON MONOXIDE, COMPRESSED 1TF 3760 X X X X 5 u 1023 COAL GAS, COMPRESSED 1TF X X X X 5 1045 FLUORINE, COMPRESSED 1TOC 185 X X 5 200 30 a, k, n, o 1046 HELIUM, COMPRESSED 1A X X X X 10 ua, va 1049 HYDROGEN, COMPRESSED 1F X X X X 10 d, ua, va 1056 KRYPTON, COMPRESSED 1A X X X X 10 ua, va 1065 NEON, COMPRESSED 1A X X X X 10 ua, va 1066 NITROGEN, COMPRESSED 1A X X X X 10 ua, va 1071 OIL GAS, COMPRESSED 1TF X X X X 5 1072 OXYGEN, COMPRESSED 1O X X X X 10 s, ua, va 1612 HEXAETHYL TETRAPHOSPHATE AND COMPRESSED GAS MIXTURE 1T X X X X 5 z 1660 NITRIC OXIDE, COMPRESSED 1TOC 115 X X 5 225 33 k, o 1953 COMPRESSED GAS, TOXIC, FLAMMABLE, N.O.S. 1TF  5000 X X X X 5 z 1954 COMPRESSED GAS, FLAMMABLE, N.O.S 1F X X X X 10 z, ua, va 1955 COMPRESSED GAS, TOXIC, N.O.S. 1T  5000 X X X X 5 z 1956 COMPRESSED GAS, N.O.S. 1A X X X X 10 z, ua, va 1957 DEUTERIUM, COMPRESSED 1F X X X X 10 d, ua, va 1964 HYDROCARBON GAS MIXTURE, COMPRESSED, N.O.S. 1F X X X X 10 z, ua, va 1971 METHANE, COMPRESSED or NATURAL GAS, COMPRESSED with high methane content 1F X X X X 10 ua, va 2034 HYDROGEN AND METHANE MIXTURE, COMPRESSED 1F X X X X 10 d, ua, va 2190 OXYGEN DIFLUORIDE, COMPRESSED 1TOC 2.6 X X 5 200 30 a, k, n, o d Not applicable for pressure receptacles made of composite materials. e Where the entries are blank, the working pressure shall not exceed two thirds of the test pressure. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 1: COMPRESSED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar e Maximum working pressure, bar e Special packing provisions 3156 COMPRESSED GAS, OXIDIZING, N.O.S. 1O X X X X 10 z, ua, va 3303 COMPRESSED GAS, TOXIC, OXIDIZING, N.O.S. 1TO  5000 X X X X 5 z 3304 COMPRESSED GAS, TOXIC, CORROSIVE, N.O.S. 1TC  5000 X X X X 5 z 3305 COMPRESSED GAS, TOXIC, FLAMMABLE, CORROSIVE, N.O.S. 1TFC  5000 X X X X 5 z 3306 COMPRESSED GAS, TOXIC, OXIDIZING, CORROSIVE, N.O.S. 1TOC  5000 X X X X 5 z d Not applicable for pressure receptacles made of composite materials. e Where the entries are blank, the working pressure shall not exceed two thirds of the test pressure. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 1001 ACETYLENE, DISSOLVED 4F X X 10 60 c, p 1005 AMMONIA, ANHYDROUS 2TC 4000 X X X X 5 29 0.54 b, ra 1008 BORON TRIFLUORIDE 2TC 864 X X X X 5 225 0.715 a 300 0.86 a 1009 BROMOTRIFLUORO-METHANE (REFRIGERANT GAS R 13B1) 2A X X X X 10 42 1.13 ra 120 1.44 ra 250 1.60 ra 1010 BUTADIENES, STABILIZED (1,2-butadiene) or 2F X X X X 10 10 0.59 ra BUTADIENES, STABILIZED (1,3-butadiene) or 2F X X X X 10 10 0.55 ra BUTADIENES AND HYDROCARBON MIXTURE, STABILIZED 2F X X X X 10 10 0.50 ra, v, z 1011 BUTANE 2F X X X X 10 10 0.52 ra, v 1012 BUTYLENE (Butylenes mixture) or 2F X X X X 10 10 0.50 ra, z BUTYLENE (1-Butylene) or 2F X X X X 10 10 0.53 ra BUTYLENE (cis-2-Butylene) or 2F X X X X 10 10 0.55 ra BUTYLENE (trans-2-Butylene) 2F X X X X 10 10 0.54 ra 1013 CARBON DIOXIDE 2A X X X X 10 190 0.68 ra, ua, va 250 0.76 ra, ua, va 1017 CHLORINE 2TOC 293 X X X X 5 22 1.25 a, ra 1018 CHLORODIFLUORO-METHANE (REFRIGERANT GAS R 22) 2A X X X X 10 27 1.03 ra 1020 CHLOROPENTAFLUORO-ETHANE (REFRIGERANT GAS R 115) 2A X X X X 10 25 1.05 ra 1021 1-CHLORO-1,2,2,2-TETRAFLUOROETHANE (REFRIGERANT GAS R 124) 2A X X X X 10 11 1.20 ra 1022 CHLOROTRIFLUORO-METHANE (REFRIGERANT GAS R 13) 2A X X X X 10 100 0.83 ra 120 0.90 ra 190 1.04 ra 250 1.11 ra 1026 CYANOGEN 2TF 350 X X X X 5 100 0.70 ra, u 1027 CYCLOPROPANE 2F X X X X 10 18 0.55 ra 1028 DICHLORODIFLUORO-METHANE (REFRIGERANT GAS R 12) 2A X X X X 10 16 1.15 ra d Not applicable for pressure receptacles made of composite materials. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 1029 DICHLOROFLUORO-METHANE (REFRIGERANT GAS R 21) 2A X X X X 10 10 1.23 ra 1030 1,1-DIFLUOROETHANE (REFRIGERANT GAS R 152a) 2F X X X X 10 16 0.79 ra 1032 DIMETHYLAMINE, ANHYDROUS 2F X X X X 10 10 0.59 b, ra 1033 DIMETHYL ETHER 2F X X X X 10 18 0.58 ra 1035 ETHANE 2F X X X X 10 95 0.25 ra 120 0.30 ra 300 0.40 ra 1036 ETHYLAMINE 2F X X X X 10 10 0.61 b, ra 1037 ETHYL CHLORIDE 2F X X X X 10 10 0.80 a, ra 1039 ETHYL METHYL ETHER 2F X X X X 10 10 0.64 ra 1040 ETHYLENE OXIDE, or ETHYLENE OXIDE WITH NITROGEN up to a total pressure of 1 MPa (10 bar) at 50 °C 2TF 2900 X X X X 5 15 0.78 l, ra 1041 ETHYLENE OXIDE AND CARBON DIOXIDE MIXTURE with more than 9 % but not more than 87 % ethylene oxide 2F X X X X 10 190 0.66 ra 250 0.75 ra 1043 FERTILIZER AMMONIATING SOLUTION with free ammonia 4A X X X 5 b, z 1048 HYDROGEN BROMIDE, ANHYDROUS 2TC 2860 X X X X 5 60 1.51 a, d, ra 1050 HYDROGEN CHLORIDE, ANHYDROUS 2TC 2810 X X X X 5 100 0.30 a, d, ra 120 0.56 a, d, ra 150 0.67 a, d, ra 200 0.74 a, d, ra 1053 HYDROGEN SULPHIDE 2TF 712 X X X X 5 48 0.67 d, ra, u 1055 ISOBUTYLENE 2F X X X X 10 10 0.52 ra 1058 LIQUEFIED GASES, nonflammable, charged with nitrogen, carbon dioxide or air 2A X X X X 10 ra, z d Not applicable for pressure receptacles made of composite materials. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 1060 METHYLACETYLENE AND PROPADIENE MIXTURE, STABILIZED 2F X X X X 10 c, ra, z Propadiene with 1 % to 4 % methylacetylene 2F X X X X 10 22 0.52 c, ra Mixture P1 2F X X X X 10 30 0.49 c, ra Mixture P2 2F X X X X 10 24 0.47 c, ra 1061 METHYLAMINE, ANHYDROUS 2F X X X X 10 13 0.58 b, ra 1062 METHYL BROMIDE with not more than 2 % chloropicrin 2T 850 X X X X 5 10 1.51 a 1063 METHYL CHLORIDE (REFRIGERANT GAS R 40) 2F X X X X 10 17 0.81 a, ra 1064 METHYL MERCAPTAN 2TF 1350 X X X X 5 10 0.78 d, ra, u 1067 DINITROGEN TETROXIDE (NITROGEN DIOXIDE) 2TOC 115 X X X 5 10 1.30 k 1069 NITROSYL CHLORIDE 2TC 35 X X 5 13 1.10 k, ra 1070 NITROUS OXIDE 2O X X X X 10 180 0.68 ua, va 225 0.74 ua, va 250 0.75 ua, va 1075 PETROLEUM GASES, LIQUEFIED 2F X X X X 10 v, z 1076 PHOSGENE 2TC 5 X X X 5 20 1.23 a, k, ra 1077 PROPYLENE 2F X X X X 10 27 0.43 ra 1078 REFRIGERANT GAS, N.O.S. 2A X X X X 10 ra, z Mixture F1 2A X X X X 10 12 1.23 ra, z Mixture F2 2A X X X X 10 18 1.15 ra, z Mixture F3 2A X X X X 10 29 1.03 ra, z 1079 SULPHUR DIOXIDE 2TC 2520 X X X X 5 12 1.23 ra 1080 SULPHUR HEXAFLUORIDE 2A X X X X 10 70 1.06 ra, ua, va 140 1.34 ra, ua, va 160 1.38 ra, ua, va 1081 TETRAFLUOROETHYLENE, STABILIZED 2F X X X X 10 200 m, o, ra 1082 TRIFLUOROCHLOROETHY-LENE, STABILIZED (REFRIGERANT GAS R1113) 2TF 2000 X X X X 5 19 1.13 ra, u 1083 TRIMETHYLAMINE, ANHYDROUS 2F X X X X 10 10 0.56 b, ra 1085 VINYL BROMIDE, STABILIZED 2F X X X X 10 10 1.37 a, ra d Not applicable for pressure receptacles made of composite materials. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 1086 VINYL CHLORIDE, STABILIZED 2F X X X X 10 12 0.81 a, ra 1087 VINYL METHYL ETHER, STABILIZED 2F X X X X 10 10 0.67 ra 1581 CHLOROPICRIN AND METHYL BROMIDE MIXTURE with more than 2 % chloropicrin 2T 850 X X X X 5 10 1.51 a 1582 CHLOROPICRIN AND METHYL CHLORIDE MIXTURE 2T f X X X X 5 17 0.81 a 1589 CYANOGEN CHLORIDE, STABILIZED 2TC 80 X X 5 20 1.03 k 1741 BORON TRICHLORIDE 2TC 2541 X X X X 5 10 1.19 a, ra 1749 CHLORINE TRIFLUORIDE 2TOC 299 X X X X 5 30 1.40 a 1858 HEXAFLUOROPROPYLENE (REFRIGERANT GAS R 1216) 2A X X X X 10 22 1.11 ra 1859 SILICON TETRAFLUORIDE 2TC 922 X X X X 5 200 0.74 a 300 1.10 a 1860 VINYL FLUORIDE, STABILIZED 2F X X X X 10 250 0.64 a, ra 1911 DIBORANE 2TF 80 X X 5 250 0.07 d, k, o 1912 METHYL CHLORIDE AND METHYLENE CHLORIDE MIXTURE 2F X X X X 10 17 0.81 a, ra 1952 ETHYLENE OXIDE AND CARBON DIOXIDE MIXTURE with not more than 9 % ethylene oxide 2A X X X X 10 190 0.66 ra 250 0.75 ra 1958 1,2-DICHLORO-1,1,2,2-TETRAFLUOROETHANE (REFRIGERANT GAS R 114) 2A X X X X 10 10 1.30 ra 1959 1,1-DIFLUOROETHYLENE (REFRIGERANT GAS R 1132a) 2F X X X X 10 250 0.77 ra 1962 ETHYLENE 2F X X X X 10 225 0.34 300 0.38 d Not applicable for pressure receptacles made of composite materials. f Considered to be toxic. The LC₅₀ value still to be determined. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 1965 HYDROCARBON GAS MIXTURE, LIQUEFIED, N.O.S 2F X X X X 10 g ra, ta, v, z Mixture A 2F 10 10 0.50 ra, ta, v, z Mixture A01 2F 10 15 0.49 ra, ta, v, z Mixture A02 2F 10 15 0.48 ra, ta, v, z Mixture A0 2F 10 15 0.47 ra, ta, v, z Mixture A1 2F 10 20 0.46 ra, ta, v, z Mixture B1 2F 10 25 0.45 ra, ta, v, z Mixture B2 2F 10 25 0.44 ra, ta, v, z Mixture B 2F 10 25 0.43 ra, ta, v, z Mixture C 2F 10 30 0.42 ra, ta, v, z 1967 INSECTICIDE GAS, TOXIC, N.O.S. 2T X X X X 5 z 1968 INSECTICIDE GAS, N.O.S. 2A X X X X 10 ra, z 1969 ISOBUTANE 2F X X X X 10 10 0.49 ra, v d Not applicable for pressure receptacles made of composite materials. g For mixtures of UN No. 1965, the maximum permissible filling mass per litre of capacity is as follows: Density at 50 °C in kg/l 0.440 0.450 0.463 0.474 0.485 0.495 0.505 0.516 0.525 Maximum permissible mass of contents per litre capacity 0.50 Mixture A MVP 1.1 MPa (11 bar) 0.49 Mixture A01 MVP 1.6 MPa (16 bar) 0.48 Mixture A02 MVP 1.6 MPa (16 bar) 0.47 Mixture A0 MVP 1.6 MPa (16 bar) 0.46 Mixture A1 MVP 2.1 MPa (21 bar) 0.45 Mixture B1 MVP 2.6 MPa (26 bar) 0.44 Mixture B2 MVP 2.6 MPa (26 bar) 0.43 Mixture B MVP 2.6 MPa (26 bar) 0.42 Mixture C MVP 3.1 MPa (31 bar) MVP = Maximum vapour pressure at 70 °C NOTE: The graph above can be used to determine the correct filling ratios for the mixtures listed in 2.2.2.3. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 1973 CHLORODIFLUOROME-THANE AND CHLOROPENTAFLUORO-ETHANE MIXTURE with fixed boiling point, with approximately 49 % chlorodifluoromethane (REFRIGERANT GAS R 502) 2A X X X X 10 31 1.01 ra 1974 CHLORODIFLUORO-BROMOMETHANE (REFRIGERANT GAS R 12B1) 2A X X X X 10 10 1.61 ra 1975 NITRIC OXIDE AND DINITROGEN TETROXIDE MIXTURE (NITRIC OXIDE AND NITROGEN DIOXIDE MIXTURE) 2TOC 115 X X X 5 k, z 1976 OCTAFLUOROCYCLO-BUTANE (REFRIGERANT GAS RC 318) 2.A X X X X 10 11 1.32 ra 1978 PROPANE 2F X X X X 10 23 0.43 ra, v 1982 TETRAFLUOROMETHANE (REFRIGERANT GAS R 14) 2A X X X X 10 200 0.71 300 0.90 1983 1-CHLORO-2,2,2-TRIFLUOROETHANE (REFRIGERANT GAS R 133a) 2A X X X X 10 10 1.18 ra 1984 TRIFLUOROMETHANE (REFRIGERANT GAS R 23) 2A X X X X 10 190 0.88 ra 250 0.96 ra 2035 1,1,1-TRIFLUOROETHANE (REFRIGERANT GAS R 143a) 2F X X X X 10 35 0.73 ra 2036 XENON 2A X X X X 10 130 1.28 2044 2,2-DIMETHYLPROPANE 2F X X X X 10 10 0.53 ra 2073 AMMONIA SOLUTION, relative density less than 0.880 at 15 °C in water, 4A with more than 35 % but not more than 40 % ammonia 4A X X X X 5 10 0.80 b with more than 40 % but not more than 50 % ammonia 4A X X X X 5 12 0.77 b 2188 ARSINE 2TF 178 X X 5 42 1.10 d, k 2189 DICHLOROSILANE 2TFC 314 X X X X 5 10 0.90 a 200 1.08 a 2191 SULPHURYL FLUORIDE 2T 3020 X X X X 5 50 1.10 u 2192 GERMANE h 2TF 620 X X X X 5 250 0.064 d, ra, r, q d Not applicable for pressure receptacles made of composite materials. h Considered as pyrophoric. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 2193 HEXAFLUOROETHANE (REFRIGERANT GAS R 116) 2A X X X X 10 200 1.13 2194 SELENIUM HEXAFLUORIDE 2TC 50 X X 5 36 1.46 k, ra 2195 TELLURIUM HEXAFLUORIDE 2TC 25 X X 5 20 1.00 k, ra 2196 TUNGSTEN HEXAFLUORIDE 2TC 218 X X X X 5 10 3.08 a, ra 2197 HYDROGEN IODIDE, ANHYDROUS 2TC 2860 X X X X 5 23 2.25 a, d, ra 2198 PHOSPHORUS PENTAFLUORIDE 2TC 261 X X X X 5 200 0.90 300 1.25 2199 PHOSPHINE h 2TF 20 X X 5 225 0.30 d, k, q, ra 250 0.45 d, k, q, ra 2200 PROPADIENE, STABILIZED 2F X X X X 10 22 0.50 ra 2202 HYDROGEN SELENIDE, ANHYDROUS 2TF 51 X X 5 31 1.60 k 2203 SILANE h 2F X X X X 10 225 0.32 q 250 0.36 q 2204 CARBONYL SULPHIDE 2TF 1700 X X X X 5 30 0.87 ra, u 2417 CARBONYL FLUORIDE 2TC 360 X X X X 5 200 0.47 300 0.70 2418 SULPHUR TETRAFLUORIDE 2TC 40 X X 5 30 0.91 a, k, ra 2419 BROMOTRIFLUORO-ETHYLENE 2F X X X X 10 10 1.19 ra 2420 HEXAFLUOROACETONE 2TC 470 X X X X 5 22 1.08 ra 2421 NITROGEN TRIOXIDE 2TOC CARRIAGE PROHIBITED 2422 OCTAFLUOROBUT-2-ENE (REFRIGERANT GAS R 1318) 2A X X X X 10 12 1.34 ra 2424 OCTAFLUOROPROPANE (REFRIGERANT GAS R 218) 2A X X X X 10 25 1.04 ra 2451 NITROGEN TRIFLUORIDE 2O X X X X 10 200 0.50 2452 ETHYLACETYLENE, STABILIZED 2F X X X X 10 10 0.57 c, ra 2453 ETHYL FLUORIDE (REFRIGERANT GAS R 161) 2F X X X X 10 30 0.57 ra 2454 METHYL FLUORIDE (REFRIGERANT GAS R 41) 2F X X X X 10 300 0.63 ra 2455 METHYL NITRITE 2A CARRIAGE PROHIBITED 2517 1-CHLORO-1,1-DIFLUOROETHANE (REFRIGERANT GAS R 142b) 2F X X X X 10 10 0.99 ra 2534 METHYLCHLOROSILANE 2TFC 2810 X X X X 5 ra, z 2548 CHLORINE PENTAFLUORIDE 2TOC 122 X X 5 13 1.49 a, k d Not applicable for pressure receptacles made of composite materials. h Considered as pyrophoric. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 2599 CHLOROTRIFLUORO-METHANE AND TRIFLUOROMETHANE AZEOTROPIC MIXTURE with approximately 60 % chlorotrifluoromethane (REFRIGERANT GAS R 503) 2A X X X X 10 31 0.12 ra 42 0.17 ra 100 0.64 ra 2601 CYCLOBUTANE 2F X X X X 10 10 0.63 ra 2602 DICHLORODIFLUORO-METHANE AND DIFLUOROETHANE AZEOTROPIC MIXTURE with approximately 74 % dichlorodifluoromethane (REFRIGERANT GAS R 500) 2A X X X X 10 22 1.01 ra 2676 STIBINE 2TF 178 X X 5 200 0.49 k, ra, r 2901 BROMINE CHLORIDE 2TOC 290 X X X X 5 10 1.50 a 3057 TRIFLUOROACETYL CHLORIDE 2TC 10 X X X 5 17 1.17 k, ra 3070 ETHYLENE OXIDE AND DICHLORODIFLUORO-METHANE MIXTURE with not more than 12,5 % ethylene oxide 2A X X X X 10 18 1.09 ra 3083 PERCHLORYL FLUORIDE 2TO 770 X X X X 5 33 1.21 u 3153 PERFLUORO(METHYL VINYL ETHER) 2F X X X X 10 20 0.75 ra 3154 PERFLUORO(ETHYL VINYL ETHER) 2F X X X X 10 10 0.98 ra 3157 LIQUEFIED GAS, OXIDIZING, N.O.S. 2O X X X X 10 z 3159 1,1,1,2-TETRAFLUOROETHANE (REFRIGERANT GAS R 134a) 2A X X X X 10 18 1.05 ra 3160 LIQUEFIED GAS, TOXIC, FLAMMABLE, N.O.S. 2TF  5000 X X X X 5 ra, z 3161 LIQUEFIED GAS, FLAMMABLE, N.O.S. 2F X X X X 10 ra, z 3162 LIQUEFIED GAS, TOXIC, N.O.S. 2T  5000 X X X X 5 z 3163 LIQUEFIED GAS, N.O.S. 2A X X X X 10 ra, z 3220 PENTAFLUOROETHANE (REFRIGERANT GAS R 125) 2A X X X X 10 49 0.95 ra 35 0.87 ra 3252 DIFLUOROMETHANE (REFRIGERANT GAS R 32) 2F X X X X 10 48 0.78 ra d Not applicable for pressure receptacles made of composite materials. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 3296 HEPTAFLUOROPROPANE (REFRIGERANT GAS R 227) 2A X X X X 10 13 1.21 ra 3297 ETHYLENE OXIDE AND CHLOROTETRAFLUORO-ETHANE MIXTURE with not more than 8.8 % ethylene oxide 2A X X X X 10 10 1.16 ra 3298 ETHYLENE OXIDE AND PENTAFLUOROETHANE MIXTURE with not more than 7.9 % ethylene oxide 2A X X X X 10 26 1.02 ra 3299 ETHYLENE OXIDE AND TETRAFLUOROETHANE MIXTURE with not more than 5.6 % ethylene oxide 2A X X X X 10 17 1.03 ra 3300 ETHYLENE OXIDE AND CARBON DIOXIDE MIXTURE with more than 87 % ethylene oxide 2TF More than 2900 X X X X 5 28 0.73 ra 3307 LIQUEFIED GAS, TOXIC, OXIDIZING, N.O.S. 2TO  5000 X X X X 5 z 3308 LIQUEFIED GAS, TOXIC, CORROSIVE, N.O.S. 2TC  5000 X X X X 5 ra, z 3309 LIQUEFIED GAS, TOXIC, FLAMMABLE, CORROSIVE, N.O.S. 2TFC  5000 X X X X 5 ra, z 3310 LIQUEFIED GAS, TOXIC, OXIDIZING, CORROSIVE, N.O.S. 2TOC  5000 X X X X 5 z 3318 AMMONIA SOLUTION, relative density less than 0.880 at 15 °C in water, with more than 50 % ammonia 4TC X X X X 5 b 3337 REFRIGERANT GAS R 404A (Pentafluoroethane, 1,1,1-trifluoroethane, and 1,1,1,2-tetrafluoroethane zeotropic mixture with approximately 44 % pentafluoroethane and 52 % 1,1,1-trifluoroethane) 2A X X X X 10 36 0.82 ra 3338 REFRIGERANT GAS R 407A (Difluoromethane, pentafluoroethane, and 1,1,1,2-tetrafluoroethane zeotropic mixture with approximately 20 % difluoromethane and 40 % pentafluoroethane) 2A X X X X 10 32 0.94 ra d Not applicable for pressure receptacles made of composite materials. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 2: LIQUEFIED GASES AND DISSOLVED GASES UN No. Name and description Classification code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 3339 REFRIGERANT GAS R 407B (Difluoromethane, pentafluoroethane, and 1,1,1,2-tetrafluoroethane zeotropic mixture with approximately 10 % difluoromethane and 70 % pentafluoroethane 2A X X X X 10 33 0.93 ra 3340 REFRIGERANT GAS R 407C (Difluoromethane, pentafluoroethane, and 1,1,1,2-tetrafluoroethane zeotropic mixture with approximately 23 % difluoromethane and 25 % pentafluoroethane) 2A X X X X 10 30 0.95 ra 3354 INSECTICIDE GAS, FLAMMABLE, N.O.S 2F X X X X 10 ra, z 3355 INSECTICIDE GAS, TOXIC, FLAMMABLE, N.O.S. 2TF X X X X 5 ra, z 3374 ACETYLENE, SOLVENT FREE 2F X X 5 60 c, p 3553 DISILANE h 2F X X X X 10 225 0.39 q d Not applicable for pressure receptacles made of composite materials. h Considered as pyrophoric. Cont'd on next page P200 PACKING INSTRUCTION (cont'd) P200 Table 3: SUBSTANCES NOT IN CLASS 2 UN No. Name and description Class Classification Code LC₅₀ ml/m³ Cylinders Tubes Pressure drums Bundles of cylinders Test period, years d Test pressure, bar Filling ratio Special packing provisions 1051 HYDROGEN CYANIDE, STABILIZED containing less than 3 % water 6.1 TF1 40 X X 5 100 0.55 k 1052 HYDROGEN FLUORIDE, ANHYDROUS 8 CT1 1307 X X X 5 10 0.84 a, ab, ac 1745 BROMINE PENTAFLUORIDE 5.1 OTC 25 X X X 5 10 i k, ab, ad 1746 BROMINE TRIFLUORIDE 5.1 OTC 50 X X X 5 10 i k, ab, ad 2495 IODINE PENTAFLUORIDE 5.1 OTC 120 X X X 5 10 i k, ab, ad d Not applicable for pressure receptacles made of composite materials. i A minimum ullage of 8 % by volume is required.

Substances with packing instruction P200